HVAC PRO Duct · Voltage · Refrigerant Get the App

R-22 PT Chart: Pressure, Temperature and Worked Readings

By PLAYRIOT LLC · Updated

On this R-22 PT chart, 40°F corresponds to about 68.5 psig and 100°F to 195.9 psig. These are saturation reference points, not charging targets. Match the refrigerant on the nameplate before using the table.

The table below shares its stored data with our superheat and subcooling calculator. Manufacturer references are linked at the foot of this page. They can differ slightly from the stored table; follow the equipment maker’s chart for service work.

Use the superheat & subcooling calculator to work through your readings alongside this guide. It shows the result and the formula in your browser.

Free calculator · runs in your browser Run the numbers: Superheat & Subcooling Calculator Open →

R-22 pressure-temperature table: °F to psig

Saturation temp (°F) R-22 (psig)
-20 10.1
-10 16.5
0 24.0
10 32.8
20 43.0
30 54.9
40 68.5
50 84.0
60 101.6
70 121.4
80 143.6
90 168.4
100 195.9
110 226.4
120 259.9
130 296.8
140 337.3
150 381.5

Read a row as a saturation temperature and its matching gauge pressure. Psig is gauge pressure, not absolute pressure. Do not use this chart with a gauge set to psia. The Daikin chart labels its pressure units explicitly. Values between stored rows use straight-line interpolation; values outside the table are not covered.

Arkema’s manufacturer chart gives 68.6 psig at 40°F and 195.9 psig at 100°F. The stored table here gives 68.5 and 195.9. This is a reference comparison, not an instruction to change a charge to remove a tenth of a psi.

Three readings, three different jobs

These are worked examples using the stored table, not target values for a particular unit.

Job Pressure Saturation temperature Measured line temperature Result
Superheat 68.5 psig 40°F 52°F suction 12°F superheat
Superheat 84.0 psig 50°F 61°F suction 11°F superheat
Subcooling 195.9 psig 100°F 90°F liquid 10°F subcooling

Superheat = suction-line temperature − vapor saturation temperature. Subcooling = liquid saturation temperature − liquid-line temperature. Read the superheat method and subcooling method for where those measurements fit. These definitions are also shown in Fieldpiece’s SM380V operator’s manual linked below.

Write the measured pressure, selected refrigerant, saturation temperature and line temperature on the same job note. That leaves a checkable calculation instead of a bare result whose inputs have been lost.

A reading between chart rows

At 76.25 psig, the stored R-22 table is halfway between 68.5 psig at 40°F and 84.0 psig at 50°F. Linear interpolation gives 45°F. A 57°F suction line then gives 12°F superheat.

The halfway shortcut works here because the pressure was chosen exactly halfway between the two stored rows. For any other reading, find the fraction of the pressure interval first, then apply that fraction to the temperature interval. The free calculator does that lookup. Do not extend the last interval beyond the published range.

An edge case: a pressure beyond the last table row must return an out-of-range message, not a guessed saturation temperature. A pressure reading of 999 psig is outside this table. Recheck the selected refrigerant and units before using any result.

Keep the chart separate from the charging target

A P-T chart answers “what saturation temperature goes with this pressure?” It does not answer “how much refrigerant should I add?” Keep those two questions separate. Record the lookup first, then use the unit’s charging instructions and target.

For the method choice, use our TXV and fixed-orifice guide. For another refrigerant, open its own table: R-454B bubble and dew or R-32. A similar-looking pressure is not permission to substitute a chart. Daikin’s reference explicitly says to use the refrigerant marked on the nameplate and not mix refrigerants.

When recording a job, keep the source chart with the readings. If a manufacturer value and an app value differ, compare refrigerant, units, liquid/vapor column and table spacing before treating either number as a diagnosis.

Match the nameplate refrigerant: use the R-410A P-T chart, R-22 P-T chart, R-32 chart or R-454B bubble and dew chart.

Keep the method in context: read R-410A PT Chart and R-454B PT Chart. The HVAC calculator app brings these field calculations onto your iPhone or iPad.

Quick answers

What pressure is R-22 at 40°F?

This site’s stored table gives about 68.5 psig at 40°F. That is a saturation reference, not a recommended running pressure. Use the equipment maker’s chart and the correct units for service work.

Can I use the R-22 chart for another refrigerant?

Use the chart for the refrigerant marked on the unit. Daikin’s reference lists separate data for R-22, R-410A, R-32 and R-454B and warns against mixing refrigerants.

Sources & standards

Related guides

The math, already on your phone

Duct sizing is listed as a Pro feature. See the App Store and in-app offer for current access, plans and eligibility.

Download on the App Store Free download · iOS 17+