Superheat & Subcooling Calculator

Enter the gauge pressure and the line temperature. It looks up saturation on the P-T chart for your refrigerant (the right column on blends like R-454B), does the subtraction, and tells you whether the number is in range for the metering device. Free, no sign-up. Updated 2026-09-29

Low-side gauge at the suction service port
psig
Clamp probe 4–6 in. from the compressor, insulated
°F
Sets what "in range" means

Result · Superheat

12.4 °F superheat
In range

Normal TXV range

A TXV self-regulates to roughly 8–12°F, so this reading says the valve is doing its job. Charge a TXV system by subcooling, not superheat.

Refrigerant
R-410A
Suction pressure
118.0 psig
Saturation temp
39.6 °F
Suction-line temp
52.0 °F
Superheat
12.4 °F

Formula Superheat = suction-line temperature − saturation (dew) temperature at suction pressure Source HVAC School, Superheat and Subcooling Basics

How the superheat calculation works

Superheat = suction-line temperature − saturation temperature. The saturation temperature is the boiling point of the refrigerant at the pressure on your low-side gauge, read off the P-T chart. On R-410A, 118 psig is about 40°F; a suction line reading 52°F means the vapor picked up 12°F of heat after it finished boiling in the coil. That is superheat. It proves the coil is fully boiling the refrigerant (no liquid reaching the compressor) without being starved.

Subcooling = saturation temperature − liquid-line temperature. Same lookup on the high side: the condensing temperature at your liquid-line pressure, minus what the liquid line actually measures at the condenser outlet. It tells you how much fully-condensed liquid is stacked up in the condenser, which is why it tracks charge on a TXV system.

Both readings need the system running 15 minutes or more so pressures settle, and an insulated clamp probe on clean copper. A bare probe in sunlight will lie to you by several degrees.

Which reading to charge by

Saturation temperatures at common gauge readings

Generated from the same tables the calculator uses (CoolProp 7.2.0; R-22 from the DuPont saturation table). R-454B uses the dew column for suction and the bubble column for liquid readings.

Suction psigR-410A dew °FR-454B dew °FR-32 dew °FR-22 dew °F
9026312553
10031363059
11036413564
11840453968
12543484272
13547524676
14551565081
16056625587
Liquid psigR-410A bubble °FR-454B bubble °FR-32 bubble °FR-22 bubble °F
250848782117
300969994131
325101105100137
350107110105143
375112115110149
400116120115—
425121125119—
450125129124—

A dash means the reading is outside that refrigerant's table (R-22 runs far lower than the A2L refrigerants at the same temperature).

Quick answers

What is normal superheat for an air conditioner?

It depends on the metering device. A TXV system self-regulates to roughly 8–12°F of superheat. A fixed-orifice (piston) system has no fixed number: the target moves with indoor wet bulb and outdoor dry bulb, usually landing between 5 and 25°F. Use the Target tab to get today's number.

What should subcooling be on an R-410A system?

Most residential R-410A TXV systems target 10–12°F of subcooling at the condenser outlet; some high-efficiency units spec up to 16°F. The number on the nameplate or charging chart overrides any rule of thumb, and you are in spec within about ±3°F of it.

Which column do I use for R-454B: bubble or dew?

Dew (vapor) for superheat on the suction line, bubble (liquid) for subcooling on the liquid line. R-454B is a zeotropic blend with about 1.5°F of glide, so the two columns differ. This calculator picks the right column for you.

Do I charge a TXV system by superheat or subcooling?

Subcooling. A TXV holds superheat roughly constant no matter how much charge is in the system, so superheat will not tell you where the charge sits. Fixed-orifice systems are the opposite: charge those by superheat against the target for today's conditions.

What does negative superheat mean?

Liquid refrigerant is leaving the evaporator and heading for the compressor (flood-back). Shut it down and look at charge, the metering device, and indoor airflow before it damages the compressor.

How accurate is the target superheat formula?

The [(3 × indoor WB) − 80 − outdoor DB] ÷ 2 approximation lands close to manufacturer charging charts across normal conditions. When the manufacturer publishes its own chart or slide rule for the unit, use that number instead.