R-454B PT Chart: Pressure-Temperature Table + How to Use It
Updated September 25, 2026
R-454B is a zeotropic blend (68.9% R-32 / 31.1% R-1234yf, ASHRAE 34 class A2L), so its PT chart has two columns: bubble point (liquid) and dew point (vapor). Use the dew column with suction pressure for superheat; use the bubble column with liquid-line pressure for subcooling. Quick reference: at 40 F, bubble is 113 psig and dew is 108 psig; at 100 F, bubble is 303 psig and dew is 292 psig; at 120 F, bubble is 399 psig and dew is 386 psig. R-454B runs a few percent lower than R-410A at the same temperature: about 5% lower on the bubble side and 8-10% lower on the dew side.
Download the printable R-454B PT chart (PDF, one page) for the truck or the jobsite. The full -40 F to 140 F table in 5 F steps is below, computed with CoolProp and cross-checked against the Honeywell Solstice 454B chart.
R-454B PT chart, -40 F to 140 F (5 F steps)
Saturation pressures in psig. Values computed with CoolProp (R454B.mix mixture model) and cross-checked against the Honeywell Solstice 454B published chart and supplier charts; agreement is within about 1 psi across the working range. The R-410A column is the liquid (bubble) pressure of R-410A at the same temperature, so you can see the gap at a glance. Manufacturer charts round differently, so treat these as reference values and confirm against the chart on the jug or the equipment's charging chart when it matters.
| Temp (F) | Bubble / Liquid (psig) | Dew / Vapor (psig) | R-410A (psig) |
|---|---|---|---|
| -40 | 9.8 | 8.5 | 10.8 |
| -35 | 13.0 | 11.5 | 14.1 |
| -30 | 16.6 | 14.9 | 17.8 |
| -25 | 20.5 | 18.6 | 21.9 |
| -20 | 24.7 | 22.7 | 26.3 |
| -15 | 29.4 | 27.1 | 31.2 |
| -10 | 34.5 | 32.0 | 36.5 |
| -5 | 40.0 | 37.2 | 42.2 |
| 0 | 45.9 | 42.9 | 48.4 |
| 5 | 52.4 | 49.1 | 55.2 |
| 10 | 59.3 | 55.7 | 62.4 |
| 15 | 66.8 | 62.9 | 70.3 |
| 20 | 74.8 | 70.6 | 78.7 |
| 25 | 83.5 | 78.9 | 87.7 |
| 30 | 92.7 | 87.8 | 97.4 |
| 35 | 102.6 | 97.3 | 107.7 |
| 40 | 113.2 | 107.5 | 118.8 |
| 45 | 124.5 | 118.3 | 130.6 |
| 50 | 136.4 | 129.9 | 143.2 |
| 55 | 149.2 | 142.2 | 156.5 |
| 60 | 162.7 | 155.3 | 170.7 |
| 65 | 177.1 | 169.2 | 185.8 |
| 70 | 192.3 | 183.9 | 201.8 |
| 75 | 208.4 | 199.5 | 218.7 |
| 80 | 225.4 | 216.0 | 236.5 |
| 85 | 243.4 | 233.5 | 255.4 |
| 90 | 262.3 | 251.9 | 275.4 |
| 95 | 282.3 | 271.4 | 296.4 |
| 100 | 303.3 | 291.9 | 318.5 |
| 105 | 325.4 | 313.5 | 341.9 |
| 110 | 348.6 | 336.3 | 367.1 |
| 115 | 373.0 | 360.3 | 392.3 |
| 120 | 398.6 | 385.5 | 419.4 |
| 125 | 425.5 | 412.1 | 447.9 |
| 130 | 453.6 | 440.0 | 477.9 |
| 135 | 483.9 | 469.3 | 509.4 |
| 140 | 514.1 | 500.2 | 542.5 |
Both columns are gauge pressure (psig) at saturation. A running system will not sit exactly on these numbers; operating pressures depend on load, airflow, and outdoor conditions. The chart tells you the saturation temperature that corresponds to a measured pressure, and the diagnosis comes from comparing that to your measured line temperatures.
Reverse lookup: gauge reading to saturation temperature
Most of the time you are holding a pressure and want the temperature, not the other way round. These are the common gauge readings converted for you.
Suction (low side) reading, use the dew column:
| Suction psig | Evaporator dew temp (F) |
|---|---|
| 90 | 31 |
| 100 | 36 |
| 107 | 40 |
| 110 | 41 |
| 120 | 46 |
| 130 | 50 |
| 140 | 54 |
| 150 | 58 |
So the dew point temperature of R-454B at 107 psig is approximately 40 F, which is the classic evaporator target on a residential system.
Liquid line (high side) reading, use the bubble column:
| Liquid psig | Condensing bubble temp (F) |
|---|---|
| 250 | 87 |
| 300 | 99 |
| 325 | 105 |
| 350 | 110 |
| 375 | 115 |
| 400 | 120 |
| 425 | 125 |
| 450 | 129 |
| 500 | 138 |
Subtract measured liquid-line temperature from the bubble temperature to get subcooling. Subtract the dew temperature from measured suction-line temperature to get superheat.
Normal R-454B operating pressures on a running AC
On a typical residential split system in cooling mode with a clean coil and correct airflow, expect roughly:
| Outdoor temp | Suction (psig, dew) | Liquid (psig, bubble) |
|---|---|---|
| 75 F | 105-120 (39-46 F evap) | 280-330 (95-106 F cond) |
| 85 F | 110-125 (41-48 F evap) | 320-370 (104-114 F cond) |
| 95 F | 115-135 (43-52 F evap) | 360-420 (112-124 F cond) |
| 105 F | 120-140 (45-54 F evap) | 400-460 (120-131 F cond) |
These are ballpark ranges built from the PT table plus the usual design rules: the evaporator runs about 35 F below indoor return-air temperature and the condenser about 15-30 F above outdoor ambient. They are not charging targets. Charge is verified by superheat (fixed orifice) or subcooling (TXV/EEV) against the manufacturer's charging chart, never by chasing a pressure number. If pressures sit well outside these bands, look for airflow, a dirty coil, a restriction, or a bad reading before touching the charge.
R-454B vs R-410A pressures side by side
R-454B was picked as the closest low-GWP match to R-410A, and the pressures show it. At the same saturation temperature R-454B runs a few percent lower: about 5% on the bubble side and 8-10% on the dew side, because the glide splits the difference in R-410A's favor on the vapor column. You will hear techs say it runs higher; the saturation data says otherwise. GWP is 466, about 78% below R-410A's 2,088, which is why it is replacing R-410A in new residential equipment under the AIM Act phasedown.
| Temp (F) | R-454B bubble | R-454B dew | R-410A | R-454B bubble vs R-410A |
|---|---|---|---|---|
| 0 | 45.9 | 42.9 | 48.4 | -5% |
| 40 | 113.2 | 107.5 | 118.8 | -5% |
| 80 | 225.4 | 216.0 | 236.5 | -5% |
| 100 | 303.3 | 291.9 | 318.5 | -5% |
| 120 | 398.6 | 385.5 | 419.4 | -5% |
| 140 | 514.1 | 500.2 | 542.5 | -5% |
Practical consequences:
- Gauges and hoses rated for R-410A are fine on pressure, but manifold scales and digital probes must have an R-454B bubble/dew profile or your readings are off by the glide.
- Lower pressure does not mean it is a drop-in. R-454B is mildly flammable (A2L). It is only legal in equipment listed for it under UL 60335-2-40. Charge limits, refrigerant sensors and mitigation logic in A2L equipment are part of the listing.
- Recovery and storage need A2L-rated recovery machines and cylinders (left-hand thread, red band). Vacuum pumps and scales are the same.
- Superheat and subcooling targets on an R-454B unit come from that unit's charging chart. Do not carry over an R-410A target from memory.
- Do not eyeball R-410A numbers from memory. An 8-10% suction-side gap reads like a low charge if you are mentally on the wrong chart.
(R-410A values from the same CoolProp property engine; R-410A's glide is under 0.5 F, so one column covers it.)
Why R-454B has two columns: bubble vs dew
R-454B is a zeotropic blend of 68.9% R-32 and 31.1% R-1234yf by weight. The two components don't boil at the same temperature, so at any given pressure the blend starts boiling at one temperature (the bubble point) and finishes at a higher one (the dew point). That spread is the temperature glide — about 1.5 C (roughly 2.5-2.7 F) for R-454B at typical operating pressures, per the CoolProp mixture model and Honeywell's published data. Small compared to something like R-407C, but big enough that using the wrong column costs you 2-3 F of accuracy on every reading.
The rule, straight from Honeywell's Solstice 454B application guidance:
- Dew point column — vapor side. Use it with suction pressure for superheat and evaporator saturation temperature.
- Bubble point column — liquid side. Use it with liquid-line pressure for subcooling and condensing temperature.
A single-column R-454B chart or gauge scale is averaging the glide away. That's a built-in 1-1.5 F error on both superheat and subcooling before you've measured anything. With a blend, always work from a two-column chart or a gauge set with proper bubble/dew scales.
Using the chart on the job: superheat and subcooling
Same procedure as any refrigerant — the only change from R-410A habits is picking the right column.
Superheat (vapor side — dew column):
Superheat (F) = suction line temperature (F) − dew saturation temperature (F)
Example: suction gauge reads 130 psig. From the dew column, 130 psig is about 50 F saturation. Strap a probe on the suction line near the condensing unit and read 60 F. Superheat = 60 F − 50 F = 10 F.
Subcooling (liquid side — bubble column):
Subcooling (F) = bubble saturation temperature (F) − liquid line temperature (F)
Example: liquid-line gauge reads 349 psig. From the bubble column, that's about 110 F saturation. Liquid line measures 100 F at the service valve. Subcooling = 110 F − 100 F = 10 F.
Charging targets don't come from the PT chart — they come from the equipment. Charge TXV/EEV systems to the subcooling target on the data plate or charging chart; charge fixed-orifice systems to the manufacturer's target-superheat table for the measured indoor wet-bulb and outdoor dry-bulb. Those manufacturer tables are already built for R-454B on new equipment — the PT chart's job is converting your gauge reading into a saturation temperature you can trust.
A2L handling: mildly flammable, not business as usual
R-454B is ASHRAE Standard 34 class A2L — lower toxicity, mildly flammable, burning velocity 10 cm/s or less. It is hard to ignite and doesn't sustain a flame easily, but it is not an A1 like R-410A, and the work rules change:
- A2L-rated recovery machine, hoses, and leak detector. Standard R-410A recovery units aren't rated for flammable refrigerants. Never vent — EPA Section 608 recovery rules apply to R-454B like any other refrigerant.
- No ignition sources in the work zone. Flow nitrogen while brazing (good practice on any system, mandatory habit here), and check with your A2L detector before lighting a torch on a system that held charge.
- New equipment only. R-454B is not a drop-in for R-410A systems. A2L equipment is listed to UL 60335-2-40, with charge limits and, on some systems, refrigerant leak-detection sensors that drive the blower to dissipate a leak. Retrofitting an A2L into an A1-listed system violates the listing.
- Cylinders are marked. A2L jugs carry a red band on the shoulder flagging the flammability class, and they still ship with standard service threads.
None of this is exotic — it's the same discipline R-32 split systems have run on overseas for years. Get the A2L-rated tools, keep ignition sources out of the work zone, and the PT chart work is identical to what you already do.
Quick answers
What is the dew point temperature of R-454B at 107 psig?
About 40 F. On the R-454B dew (vapor) column, 107.5 psig corresponds to 40 F saturation, which is why 105-110 psig suction is the classic evaporator target on a residential system. Use the dew column for any suction-side reading.
What should R-454B pressures be on a running AC system?
On a typical residential system in cooling, expect suction pressure around 110-135 psig (a 40-45 F evaporator dew temperature) and liquid pressure around 335-425 psig (a 105-125 F condensing bubble temperature), depending on outdoor temperature and load. Those are ballpark operating ranges, not targets — verify charge with superheat or subcooling against the manufacturer's charging chart, not by chasing a pressure number.
Can I put R-454B in an R-410A system?
No. R-454B is mildly flammable (A2L) and is only legal in equipment listed for it under UL 60335-2-40 — the listing covers charge limits, component ratings, and in some systems leak-dissipation sensors. An R-410A system carries none of that. Pressures being similar doesn't make it a retrofit; it's a new-equipment refrigerant.
Which column do I use for superheat on R-454B — bubble or dew?
Dew. Superheat is a vapor-side measurement, so convert suction pressure to saturation temperature using the dew (vapor) column, then subtract from measured suction line temperature. Bubble is for the liquid side — subcooling and condensing temperature. Mixing them up puts roughly a 2-3 F error on the reading because of R-454B's glide.
Is there a printable R-454B PT chart?
Yes. The one-page PDF at hvacprocalculator.com/r454b-pt-chart.pdf covers -40 F to 140 F in 5 F steps with bubble, dew and an R-410A comparison column. It is free and prints on letter paper.
Does R-454B run higher or lower pressure than R-410A?
Lower. At the same saturation temperature R-454B bubble pressure is about 5% below R-410A and dew pressure about 8-10% below. Some articles claim it runs higher; the Honeywell chart and CoolProp both show lower.
Sources & standards
Related guides
How to Calculate Superheat
The formula, where to clamp, and target ranges for fixed-orifice and TXV systems.
Read the guide →R-32 PT Chart
Saturation table for R-32, how it compares to R-410A, and A2L handling notes.
Read the guide →How to Read a PT Chart
Saturation temps, superheat and subcooling lookups, and the bubble/dew columns on blends.
Read the guide →