How to Read a PT Chart (Superheat, Subcooling, and Blends)
A PT chart maps refrigerant pressure to saturation temperature — the temperature where liquid and vapor coexist. To read it: (1) identify the refrigerant, (2) read gauge pressure in psig, (3) find that pressure on the chart, (4) read across to the saturation temperature. It gets used three ways in the field: predicting coil pressure at a given coil temperature, calculating superheat (measured suction-line temperature minus saturation temperature at suction pressure), and calculating subcooling (saturation temperature at liquid-line pressure minus measured liquid-line temperature). Single-component refrigerants (R-22, R-32) and near-azeotropes (R-410A) use one column. Zeotropic blends (R-454B, R-407C) boil across a temperature glide, so their charts carry two columns: use the dew point column for superheat on the suction side and the bubble point column for subcooling on the liquid side. Example: R-410A at 118.9 psig saturates at 40°F, so a 50°F suction line means 10°F of superheat.
What a PT Chart Actually Maps
A pressure-temperature chart maps one physical relationship: for a given refrigerant, saturation pressure and saturation temperature lock together. Saturation is the condition where liquid and vapor exist side by side — inside a running evaporator, inside a condenser, or in a cylinder sitting on the truck. Wherever both phases are present, pressure tells you temperature and temperature tells you pressure. That is the whole chart.
Two things to keep straight:
- Field charts read in psig, not psia. Your manifold reads gauge pressure and the chart is printed in gauge pressure, so they match directly at sea level. At altitude, atmospheric pressure drops roughly 0.5 psi per 1,000 ft, which starts to matter above about 5,000 ft.
- The chart only applies at saturation. Superheated vapor in the suction line and subcooled liquid in the liquid line do not follow the chart — and that is exactly why superheat and subcooling measurements work. The chart hands you the saturation point; your clamp thermometer tells you how far the actual line temperature has moved away from it.
The Three Jobs a PT Chart Does
Every field use of a PT chart is one of three moves.
1. Predict or set coil pressure. A comfort-cooling evaporator is commonly designed to run about 35°F colder than return air (the standard design TD rule of thumb), so with 75°F return air you expect a coil near 40°F — on R-410A that is 118.9 psig on the low-side gauge. On the high side, condensing temperature typically runs 15°F to 30°F above outdoor ambient depending on condenser design. If your gauges land far from those predictions, the chart just told you where to start looking.
2. Superheat (suction side). Superheat = measured suction-line temperature − saturation temperature at suction pressure (definitions per ASHRAE Fundamentals; targets come from the manufacturer's charging chart). It proves the vapor kept absorbing heat after it finished boiling — meaning no liquid is headed for the compressor. Fixed-orifice systems are charged to a target superheat off the manufacturer's charging chart.
3. Subcooling (liquid side). Subcooling = saturation temperature at liquid-line pressure − measured liquid-line temperature. It proves the liquid kept rejecting heat after it fully condensed — a solid liquid column feeding the metering device. TXV systems are charged to the manufacturer's subcooling target, commonly 8–12°F on residential equipment; the number on the unit's data plate always wins.
Single-Component Refrigerants vs. Zeotropic Blends (Bubble vs. Dew)
R-22 and R-32 are single-component refrigerants: one molecule, one boiling temperature per pressure, one column on the chart. R-410A is technically a blend (50% R-32 / 50% R-125), but it is near-azeotropic — its glide is well under 0.5°F — so charts print it as a single column and you treat it like a pure refrigerant.
Zeotropic blends are different. R-454B (68.9% R-32 / 31.1% R-1234yf) and R-407C boil and condense across a temperature range at constant pressure. That range is temperature glide — per HVAC School, the difference between the bubble point and the dew point. So the chart carries two columns per pressure:
- Bubble point — where liquid starts to boil (equivalently, where condensing finishes).
- Dew point — where the last droplet finishes boiling (equivalently, where condensing starts).
Which column goes with which reading:
| Reading | Where you measure | Column | Why |
|---|---|---|---|
| Superheat | Suction line | Dew point | Superheat begins only after boiling is complete |
| Subcooling | Liquid line | Bubble point | Subcooling begins only after condensing is complete |
| Static / standing pressure | Cylinder or off system | Bubble (liquid present) | Liquid-vapor equilibrium sits near the bubble line |
R-454B's glide is small — roughly 1.5°F to 2.5°F depending on operating range — so the wrong column costs you a degree or two. On R-407C, with roughly 8–10°F of glide, the wrong column wrecks the diagnosis outright. Build the habit on the small-glide blends so it holds on the big ones.
Worked Example: R-410A
R-410A saturation values, per the LearnMetrics R-410A PT chart and cross-checked against AC Direct's published table:
| Temp (°F) | Pressure (psig) |
|---|---|
| 20 | 78.7 |
| 30 | 97.5 |
| 35 | 107.9 |
| 40 | 118.9 |
| 45 | 130.7 |
| 50 | 143.3 |
| 90 | 274.3 |
| 95 | 295.0 |
| 100 | 316.9 |
| 105 | 339.9 |
| 110 | 364.1 |
| 115 | 389.6 |
| 120 | 416.4 |
| 125 | 444.5 |
Superheat check. The suction gauge reads 119 psig — the chart says 40°F saturation. Your insulated clamp probe on the suction line at the condensing unit reads 50°F. Superheat = 50°F − 40°F = 10°F. Vapor left the coil fully boiled and picked up 10°F of extra heat on the way to the compressor.
Subcooling check. Head pressure reads 340 psig — the chart says 105°F condensing temperature. The liquid-line probe reads 95°F. Subcooling = 105°F − 95°F = 10°F, inside the common 8–12°F TXV window — but confirm against the data plate.
Sanity-check the whole picture: with 85°F outdoor air, condensing at 105°F is a 20°F condenser split — normal territory for a mid-efficiency condenser.
Worked Example: R-454B (Zeotropic Blend)
R-454B bubble and dew values, per the LearnMetrics R-454B PT chart; a second published table at HVAC PT Charts agrees within about 1 psig. Confirm final numbers against the equipment manufacturer's chart (Honeywell publishes the Solstice 454B PT chart with the same bubble/dew layout).
| Temp (°F) | Bubble (psig) | Dew (psig) |
|---|---|---|
| 20 | 75.0 | 70.9 |
| 30 | 92.9 | 88.1 |
| 40 | 113.3 | 107.7 |
| 45 | 124.6 | 118.5 |
| 50 | 136.6 | 130.1 |
| 90 | 262.5 | 251.9 |
| 100 | 303.6 | 291.6 |
| 105 | 325.7 | 313.6 |
| 110 | 348.9 | 336.4 |
| 120 | 399.1 | 385.8 |
| 125 | 426.0 | 412.4 |
Superheat — dew column. The suction gauge reads 108 psig. In the dew column, 107.7 psig sits at 40°F. The suction line reads 49°F. Superheat = 49°F − 40°F = 9°F.
Subcooling — bubble column. Head pressure reads 326 psig. In the bubble column, 325.7 psig sits at 105°F. The liquid line reads 96°F. Subcooling = 105°F − 96°F = 9°F.
What the wrong column costs you. At 326 psig the dew column corresponds to roughly 107.5°F. Use it for subcooling by mistake and you would report about 11.5°F instead of 9°F — a 2.5°F error on a target window only 4°F wide. Make the same mistake on a big-glide blend like R-407C and the error grows to 8–10°F, enough to misdiagnose the charge completely.
Quick answers
Do I use bubble point or dew point for superheat?
Dew point. Superheat is measured against the temperature where the last droplet of liquid finishes boiling, and that is the dew point. Bubble point is for subcooling on the liquid line. On R-454B the difference is only a degree or two, but on a big-glide blend like R-407C using the wrong column throws the reading off by several degrees.
Why does R-410A only have one column when it's a blend?
R-410A is a 50/50 blend of R-32 and R-125, but the two components boil so close together that the glide is well under 0.5°F — it behaves as near-azeotropic. Chart publishers print it as a single column, and in the field you treat it exactly like a pure refrigerant.
Can I use a PT chart on a system that's off?
Yes — that is the classic gauge and charge sanity check. A cylinder or an equalized, off system that has sat long enough to reach a known ambient temperature should read close to the chart pressure for that temperature. If it reads noticeably low, suspect a leak or air contamination; if your gauge disagrees with the chart on a known-good cylinder, calibrate the gauge. On a blend with liquid present, compare against the bubble (liquid) column.
Sources & standards
- LearnMetrics — R410A PT Chart (pressure-temperature table)
- LearnMetrics — R454B PT Chart (liquid/vapor pressure-temperature table)
- HVAC PT Charts — R-454B bubble/dew table (cross-check)
- HVAC School — What Is Temperature Glide?
- HVAC School — Blends and Midpoint w/ Jim Bergmann (dew for superheat, bubble for subcooling)
- AC Direct — R-410A Pressure Temperature Chart
- Honeywell — Solstice 454B (R-454B) manufacturer PT chart (PDF)
Related guides
How to Calculate Superheat
The formula, where to clamp, and target ranges for fixed-orifice and TXV systems.
Read the guide →R-454B PT Chart
Full pressure-temperature table with bubble and dew columns, plus how glide changes your readings.
Read the guide →R-32 PT Chart
Saturation table for R-32, how it compares to R-410A, and A2L handling notes.
Read the guide →