CFM Calculator

Three ways techs actually need airflow: the target for a system's tonnage, the airflow a furnace is really delivering from its temperature rise, and the exhaust or ventilation a room needs from air changes per hour.Updated 2026-09-29

Nameplate BTU/hr ÷ 12,000. Or tap a size.
tons
Climate sets the target

Result · Airflow from tonnage

1,200 CFM
In range

Standard-air target

A 3.0-ton system at 400 CFM/ton needs about 1,200 CFM across the indoor coil. Set airflow before you touch the charge — the blower table in the install manual is the real spec.

System size
3.0 tons (36,000 BTU/hr)
Airflow per ton
400 CFM/ton
Target airflow
1,200 CFM
Acceptable band (350–450/ton)
1,050 – 1,350 CFM

Formula CFM = tons × CFM per ton (400 standard air · 350 hot-humid · 450 hot-dry) Source ACCA, 400 CFM per ton

The three CFM formulas

Airflow comes first. On a cooling call, a starved coil reads high superheat and looks like an undercharge; on a furnace, low airflow shows up as a temperature rise above the nameplate range. Confirm the CFM, then read the gauges.

Target airflow by system size

System350 CFM/ton (humid)400 CFM/ton (baseline)450 CFM/ton (dry)
1.5 ton525600675
2 ton700800900
2.5 ton8751,0001,125
3 ton1,0501,2001,350
3.5 ton1,2251,4001,575
4 ton1,4001,6001,800
5 ton1,7502,0002,250

Got the target? Size the duct that carries it.

Quick answers

How many CFM per ton of air conditioning?

400 CFM per ton is the standard-air baseline, so a 3-ton system needs about 1,200 CFM across the indoor coil. Run closer to 350 CFM/ton in hot-humid climates for more moisture removal, and up to 450 CFM/ton in hot-dry climates for more sensible cooling. The blower table in the install manual is the real spec.

How do I calculate CFM from temperature rise?

CFM = heat output (BTU/hr) ÷ (1.08 × temperature rise °F). For a gas furnace, output is input × steady-state efficiency; for electric heat, kW × 3,412. Let it run 10 minutes, keep the supply probe out of sight of the heat exchanger, and treat the result as a ballpark, not a flow-hood number.

What is the CFM formula for a room?

CFM = room volume in cubic feet × air changes per hour ÷ 60. A 10 × 8 ft bathroom with an 8 ft ceiling at 8 air changes per hour needs about 85 CFM of exhaust.

Why does the sensible heat formula use 1.08?

1.08 = 60 min/hr × 0.075 lb/ft³ (density of standard air) × 0.24 BTU/lb·°F (specific heat of air). It is only right for standard air near sea level; at altitude the air is lighter and the factor drops.

What happens if airflow is too low?

On cooling, low airflow drops the coil temperature: high superheat readings look like an undercharge, the coil can ice, and capacity falls. On heating, the furnace runs a high temperature rise and trips its limit. Set airflow before you touch the refrigerant charge.