Duct Size Calculator

An online ductulator. Enter the airflow and the friction rate; get the round duct size, or the rectangular size for the height you have room for, and a velocity verdict so you know before you hang it whether it will whistle. Galvanized metal, standard air. Updated 2026-09-29

Or tap a tonnage: 400 CFM per ton
CFM
in. wc per 100 ft of duct
Sets the velocity limits

Result · Duct size

16 in. round
In range

Good trunk velocity

859 FPM. Residential supply trunks are designed for 700–900 FPM.

Airflow
1,200 CFM
Friction rate
0.08 in. wc / 100 ft
Round diameter (calculated)
15.3 in.
Round duct to use
16 in.
Velocity in that round
859 FPM

Formula Darcy-Weisbach with the Colebrook friction factor (galvanized steel, standard air), solved for the diameter that lands on your friction rate. Rectangular: ASHRAE equivalent diameter De = 1.30 (a·b)^0.625 ÷ (a+b)^0.25 Source ASHRAE Handbook — Fundamentals, Duct Design (Darcy-Weisbach / Colebrook)

How duct sizing works

Every foot of duct costs the blower some static pressure. The friction rate is how much you are willing to spend per 100 ft of duct, in inches of water column. Pick a rate, and for any airflow there is exactly one round diameter that lands on it. This calculator solves the Darcy-Weisbach equation with the Colebrook friction factor for galvanized steel and standard air, which is the same physics behind a slide-rule ductulator and the published round-duct charts.

Round is the reference. A rectangular duct is matched by equivalent diameter, not by equal area, because a flat duct has more wall rubbing on the same air: De = 1.30 (a·b)^0.625 ÷ (a+b)^0.25 (ASHRAE). Tell the tool the height you can fit and it returns the width that gives the same friction loss as the round answer, then checks the face velocity in that rectangle.

The velocity verdict is the part a chart cannot give you. A trunk at 1,100 FPM will carry the air and it will also be heard in the living room. Residential design targets: trunks 700–900 FPM, branches 500–700, returns 500–700.

Round duct capacity chart (galvanized, standard air)

Generated by the same function the calculator runs; CFM at two common friction rates and the velocity at 0.10.

Round ductCFM at 0.08 in. wc/100 ftCFM at 0.10 in. wc/100 ftVelocity at 0.10
4 in.3337425 FPM
5 in.6068497 FPM
6 in.98111564 FPM
7 in.148168627 FPM
8 in.212240687 FPM
9 in.291329744 FPM
10 in.386436799 FPM
12 in.628709902 FPM
14 in.9471,068999 FPM
16 in.1,3511,5241,091 FPM
18 in.1,8472,0831,178 FPM
20 in.2,4422,7531,262 FPM
22 in.3,1443,5441,342 FPM
24 in.3,9594,4611,420 FPM

Quick sizes by tonnage (0.08 in. wc, supply trunk)

SystemAirflowRound trunkVelocityRectangular, 10 in. tall
1.5 ton600 CFM12 in.764 FPM12 × 10 in.
2 ton800 CFM14 in.748 FPM16 × 10 in.
2.5 ton1,000 CFM15 in.815 FPM18 × 10 in.
3 ton1,200 CFM16 in.859 FPM22 × 10 in.
3.5 ton1,400 CFM17 in.888 FPM24 × 10 in.
4 ton1,600 CFM18 in.905 FPM26 × 10 in.
5 ton2,000 CFM19 in.1,016 FPM32 × 10 in.

Trunk sizes only. Returns go one size up; branch runs to registers are sized from the room's own CFM.

Quick answers

What size duct do I need for a 3-ton AC unit?

At 400 CFM per ton a 3-ton system moves about 1,200 CFM. At a 0.08 in. wc friction rate that calls for a 16 in. round supply trunk (about 860 FPM), or a rectangular equivalent such as 18 × 12 or 20 × 10. Returns run one size larger, 18 in. round, to keep velocity near 700 FPM.

What friction rate should I use?

0.08 in. wc per 100 ft is the common residential design point for supply trunks; 0.10 suits short, simple runs. Returns and long or flex-heavy systems are often designed at 0.06 or lower. Strictly, the friction rate comes from an ACCA Manual D calculation of your available static pressure divided by the total effective length.

How fast should air move in a duct?

Residential supply trunks are designed for 700–900 FPM; branch runs 500–700 FPM; returns 500–700 FPM. Above 900–1,000 FPM you get noise at takeoffs and registers plus higher static pressure. Below 500 FPM a trunk is larger than it needs to be.

Is a rectangular duct with the same area as a round duct equivalent?

No. A rectangle has more wall for the same area, so more friction. The ASHRAE equivalent-diameter equation, De = 1.30 (a·b)^0.625 ÷ (a+b)^0.25, gives the round size with the same friction loss. An 18 × 12 rectangle equals a 16.0 in. round even though its area matches a 16.6 in. round.

Does this work for flex duct?

The chart assumes galvanized sheet metal, fully extended. Flex duct pulled tight carries about the same; flex with sag or compression can lose half its capacity. Size flex one step larger than the metal answer, and pull it tight.